Electro-Air EASASD-18ASC Guía para resolver problemas

Busca en linea o descarga Guía para resolver problemas para Filtros de aire Electro-Air EASASD-18ASC. Electro-Air EASASD-18ASC Troubleshooting guide Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 12
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 0
INSTALLATION, OPERATION AND
SERVICE INSTRUCTIONS
MODELS
ASAS-10ASC, ASAS-11ASC, ASAS-12ASC, ASAS-18ASC
GSAS-10ASC, GSAS-11ASC, GSAS-12ASC, GSAS-18ASC
ELECTRONIC AIR CLEANERS
IMPORTANT: PLEASE READ MANUAL BEFORE OPERATING UNIT
Features
Lifetime Filter System never needs replacing
Electronically removes dust, mites, pollen, pet dander, tobacco smoke, cooking smoke
and grease, mold, fungi, bacteria, and more down to 0.01 micron
Light Weight Aluminum Collecting Cells are durable and easy to maintain
Cell Guides ensure proper placement of collecting cells
Activated Carbon Filters remove unpleasant odors
Galvanized Steel Cabinet for solid vertical or horizontal installation
Durable Scratch-Resistant powder coat paint finish resists corrosion
Electronic Air Proving Switch for quick wiring
Dual Indicator Lights show Air Cleaner is working properly at a glance
FOR QUESTIONS REGARDING INSTALLATION, OPERATION & SERVICE,
CALL THE AIR CLEANER HOTLINE TOLL-FREE
1-800-267-8305
Vista de pagina 0
1 2 3 4 5 6 ... 11 12

Indice de contenidos

Pagina 1 - SERVICE INSTRUCTIONS

INSTALLATION, OPERATION AND SERVICE INSTRUCTIONS MODELS ASAS-10ASC, ASAS-11ASC, ASAS-12ASC, ASAS-18ASC GSAS-10ASC, GSAS-11ASC, GSAS-12ASC, GSAS-18AS

Pagina 2 - CONTENTS

Replacing A Tungsten Ionizing Wire Replacement wires are cut to the correct length and have eyelets at each end for easy replacement. 1. Turn OFF pow

Pagina 3

PROBLEM PROBABLE CAUSE REMEDY System fan is not on. Turn system fan on. Wiring improperly connected. Check wiring. Defective power switch.

Pagina 4

GOODMAN MANUFACTURING COMPANY, L.P. 2550 North Loop West, Suite 400, Houston, Texas 77092 FOR MORE INFORMATION, CALL THE AIR CLEANER HOTLINE TOLL FRE

Pagina 5

CONTENTS SAFETY CONSIDERATIONS 2 WHAT THE ELECTRONIC AIR CLEANER DOES 2 BENEFITS

Pagina 6

1 Dirty Air 2 Prefilter 3 Ionizing Section COMPONENTS Cabinet: Constructed of heavy gauge galvanized steel to resist

Pagina 7

UNIT A B C D E F G H ASAS-10ASC GSAS-10ASC 21 (53.0) 17 (43.5) 23 1/4 (59.0) 13 1/8 (33.5) 20 3/4 (53.0) 1 1/4 (3.0) 23 3/4 (60.5) 2 3/8 (6.0

Pagina 8

Wiring Wiring should only be performed by qualified personnel only. All wiring must comply with all applicable codes and standards. The voltage of the

Pagina 9 - Screwdriver

efficiency. The frequency of cleaning will vary from one house to another. On average, the cells should be cleaned every 3 months. 1. Remove access do

Pagina 10 - Ionizing Bar

Replacing An Air Proving Switch (APS) Before replacing the APS, turn off the power to the Air Cleaner at the source. 1. Disconnect wiring from termi

Pagina 11

Replacing The 24 V Transformer (A/ GSAS-12 and A/ GSAS-18 only) Before replacing 24 V transformer, turn off power to the Air Cleaner at the source. 1.

Pagina 12 - ELECTRONIC AIR CLEANER

Testing Voltage At Cell 1. Open access door to Air Cleaner. Air Cleaner will shut off. 2. Insert a thin shafted screwdriver 2 to 3 inches into the h

Comentarios a estos manuales

Sin comentarios